UPS Uninterrupted Power Supplies are designed for the hardware and software protection of various home, office and professional electric powered systems and equipment, against power failure and instability or disturbance(Voltage Fluctuattion, Surge, Sag, Spike..). There are two main categories of UPS the On-Line and the Standby . Each one has its advantages and the right choice for the most suitable protection is depending on the type of application and the budget involved.
On-Line CP - (S) series are On-Line UPS available in 300 - 600 - 900 - 1200 - 1500 - 2000 and 2500VA with excellent features like : On-Line Stabilization, Continuous Line Filtering, Grant and Expandable Autonomy, Battery Protection against Overchargings - Overdischargings - Frequent Dischargings, Elegant Appearance, Low Profile, Noiseless Operation, High Efficiency, Computer and SNMP Interface port + software, Spike and Noise Protection, CE markings and 2 Year Warranty. They are the professional choise for the most demading applications. | |||||||
| TECHNICAL CHARACTERISTICS | CP-300S | CP-600S | CP-900S | CP-1200S | CP-1500S | CP-2000S | CP-2500S |
| INPUT Voltage Frequency |
INPUT .... 220 -20 % / +15% VAC 50 Hz |
||||||
| OUTPUT Voltage RMS Inverter Frequency Regulation Synchronized Overload |
OUTPUT .... 220 +/- 5 % VAC 50 Hz +/- 0,5 % Continuous, Input-Line Independent With AC Mains 200 % for 20ms |
||||||
| POWER CAPACITY | 300 VA | 600 VA | 900 VA | 1200 VA | 1500 VA | 2000 VA | 2500 VA |
| BATTERY | Maintenance Free Sealed Type | ||||||
| AUTONOMY with 100 % Load with 50 % Load |
30 min. 50 min. |
15 min. 35 min. |
10 min. 30 min. |
15 min. 35 min. |
20 min. 45 min. |
12 min. 35 min. |
10 min. 25 min. |
| RECHARGE TIME | 3 Hours | 4 Hours | 6 Hours |
||||
| PROTECTION Output Overvoltage Battery Input Surge Filtering |
TYPE .... Electronic Electronic Overcharge and Overdischarge Fuse-Link Suppressors Output EMI Filters |
||||||
| LED Line Back-Up Battery Low Alarm Overload |
INDICATING .... * Normal AC Mains Operation * AC Mains Voltage Failure or Low, Power is supplied from battery * Battery is reaching the permissible discharge level... * Automatic Shutdown of the UPS is imminent due to Abnormal condition * The Output is Overloaded with equipment of Higher than Nominal UPS Power |
||||||
| SOUND ALARMS Back-Up Battery Low Overload |
TYPE OF SOUND .... Periodic Signal, 2sec Continuous Signal Continuous Signal |
||||||
| PROTECTION CLASS | IP - 20 |
||||||
| COMMUNICATION | Interface Port and Software |
||||||
| ENVIRONMENTAL CONDITION |
Operating Temperature : 0 - 40'C, Humidity : 0 - 90% non-condencing Storage Temperature : -20 to 70'C |
||||||
| All items available in stock. Customized products Upon Request. Specifications are subject to change or improvement withought prior notice.. | |||||||
Standby SB series are Standby UPS available in 400 and 600VA with excellent features like : Elegant Appearance, Low Profile, Noiseless Operation, Easy to use, Low Cost, Fast Response, High Efficiency, No Moving Parts, Spike and Noise Protection, CE markings and 2 Year Warranty. They are ideal for PCs, Cashier mashines, Weighing machines, Exchange boards, Lotto machines, Laboratory Instruments, Security Systems and other Home - Office Power sensitive equipment. | ||
| TECHNICAL CHARACTERISTICS | SB - 400 | SB - 600 |
| INPUT | ||
| Working Voltage Working Frequency |
180 - 263 VAC 50 Hz +/- 10 |
|
| Nominal Current Maximum Current |
1,7 A 2,6 A |
2,2 A 3,3 A |
| OUTPUT | ||
| Voltage RMS Inverter Frequency Inverter Waveform Synchronized Transfer Time Power Factor Overload |
230 +/- 1 % VAC 50 Hz +/- 0,1 % PWM 100 % with AC Mains 2ms typical 0,6 (cosf) 300 % for 200ms, 150 % for 500ms |
|
| Nominal Power Capacity | 400 VA | 600 VA |
| BATTERIES | Maintenance Free Sealed Type | |
| Number of Batteries Voltage Capacity |
One 12 VDC 7,2 Ah |
|
| Autonomy with 100 % Load Autonomy with 50 % Load |
15 min. 37 min. |
10 min. 25 min. |
| 90 % Recharge Time | 4 Hours | |
| GENERAL | ||
| PROTECTION Output Battery Input Surge Inverter Temperature Other |
TYPE .... Overvoltage and Short-circuit Overcharge and Overdischarge Overvoltage Lightning Suppression Overload Overtemperature Backfeed |
|
| LED Line Back-Up Battery Low Alarm |
INDICATING .... * Normal AC Mains Operation * AC Mains Voltage Failure or Low, Power is supplied from battery * Battery is reaching the permissible discharge level * Automatic Shutdown of the UPS is imminent due to Abnormal condition |
|
| SOUND ALARMS Back-Up Battery Low |
TYPE OF SOUND .... Periodic Signal, 10sec Continuous Signal |
|
| DESIGNED IN ACCORDANCE WITH | EN 50091 - 1 EN 50091 - 2 |
|
| ACOUSTIC NOISE | < 40 dB per 1 m | |
| COMMUNICATION | Interface Port and Software (OPTIONAL) |
|
| ENVIRONMENTAL CONDITION | Operating Temperature : 0 - 40'C, Humidity : 0 - 90% non-condencing Storage Temperature : -20 to 70'C |
|
| DIMENTIONS ( Hight x Width x Length ) | 225 x 130 x 325 mm | |
| WEIGHT | 12 Kgr | 13 Kgr |
| All items available in stock. Customized products Upon Request. Specifications are subject to change or improvement withought prior notice. | ||
Standby SBU series are Standby UPS available in 900 - 1200 - 1500 - 2000 and 2500VA with excellent features like : High Efficiency, Elegant Appearance, Low Profile, Noiseless Operation, Grant and Expandable Autonomy, Computer and SNMP Interface port + software, Easy to use, Fast Response, High Power Capacity, High Efficiency, Spike and Noise Protection, No Moving Parts, CE markings and 2 Year Warranty. They are ideal for Computer Networks, PCs and Peripheral Systems Laboratory Instruments, Security Systems and other Professional Power sensitive equipment of higher Power Capacity. | |||||
| TECHNICAL CHARACTERISTICS | SBU-900 | SBU-1200 | SBU-1500 | SBU-2000 | SBU-2500 |
| INPUT Voltage Frequency |
INPUT .... 180 - 263 VAC 50 Hz +/- 10 % |
||||
| OUTPUT Voltage RMS Inverter Frequency Inverter Waveform Synchronized Transfer Time Overload |
OUTPUT .... 230 +/- 1 % VAC 50 Hz +/- 0,1 % PWM 100 % with AC Mains 2ms typical 300 % for 200ms, 150 % for 500ms |
||||
| POWER CAPACITY | 900 VA | 1200 VA | 1500 VA | 2000 VA | 2500 VA |
| BATTERY | Maintenance Free Sealed Type |
||||
| AUTONOMY with 100 % Load with 50 % Load |
15 min. 40 min. |
10 min. 25 min. |
15 min. 40 min. |
12 min. 35 min. |
10 min. 25 min. |
| RECHARGE TIME | 3 Hours | 4 Hours | 6 Hours |
||
| PROTECTION Output Overvoltage Battery Input-Output Surge Filtering |
TYPE .... Electronic Electronic Overcharge and Overdischarge Fuse-Link Suppressors Output EMI Filters |
||||
| LED Line Back-Up Battery Low Alarm Overload |
INDICATING .... * Normal AC Mains Voltage Operation * AC Mains Voltage Failure or Low - Power is supplied from battery * Battery is reaching the permissible discharge level... * Automatic Shutdown of UPS is imminent due to Abnormal condition * Output is Overloaded with Higher than Nominal UPS Power |
||||
| SOUND ALARMS Back-Up Battery Low Overload |
TYPE OF SOUND .... Periodic Signal, 2sec Continuous Signal Continuous Signal |
||||
| PROTECTION CLASS | IP - 20 |
||||
| COMMUNICATION | Interface Port and Software |
||||
| ENVIRONMENTAL CONDITION |
Operating Temperature : 0 - 40'C, Humidity : 0 - 90% non-condencing Storage Temperature : -20 to 70'C |
||||
| All items available in stock. Customized products Upon Request. Specifications are subject to change or improvement withought prior notice. | |||||